Domnita F., Kapalo P.2013-10-012013-10-012013Domnita F. Head loss calculation in ventilation networks using the equivalent resistance (equal friction) method / F. Domnita, P. Kapalo // Вісник Національного університету "Львівська політехніка". – 2013. – № 756 : Теорія і практика будівництва. – С. 21–26. – Bibliography: 10 titles.https://ena.lpnu.ua/handle/ntb/20964This method may be applied in two situations: when the total air pressure drop for the system is given and when some values for the so-called economical velocity are imposed along the successive ducts. In the first case, the method consists in determining the necessary diameters for some ducts and for all the system. Thus, in this case, the total available pressure is divided to the total length of the main duct, giving as result the friction loss per meter of duct, also known as friction loss factor or specific linear pressure drop [Pa/m], which includes both major and minor losses. Цей метод може бути застосований у двох випадках: коли дано загальний перепад тиску в системі і коли наведено деякі значення так званої економічної швидкості суміжних повітроводів. У першому випадку метод полягає у визначенні необхідних діаметрів окремих труб і системи загалом. Тоді тиск в цілому ділиться на загальну довжину головного повітроводу і обчислюються втрати через тертя на метр труби, або також відомі як коефіцієнт втрат через тертя або лінійна втрата тиску, що складаються з основних і другорядних втрат.enair pressure lossventilation duct systemairflow rateequivalent resistancenomogramHead loss calculation in ventilation networks using the equivalent resistance (equal friction) methodArticle