Дослідження перенапруг під час дугових замикань на землю в електромережах 35 кВ

No Thumbnail Available

Date

2013

Journal Title

Journal ISSN

Volume Title

Publisher

Видавництво Львівської політехніки

Abstract

In this article it is researched the influence of grounding conditions of neutral of electrical network 35 kV on the level of arc overvoltage due to the theory by: Petersen, Peters - Slep'yan and Belyakov – Dzhuvarly. There were given schematic dependencies of arc overvoltage multiplicities which depend on neutral grounding, given main schematic dependencies of combustion of grounding arc. It is shown that values of arc overvoltages significantly increased with increasing of the value of the capacitive current in the electrical network. Combined condition of neutral grounding reduces the level of arc overvoltages the best. Multiplicity does not exceed 2.4 for all theories for various values of capacitive current.

Description

Keywords

електромережа, дугова перенапруга, цифрова модель, ізольована нейтраль, резонансно-заземлена нейтраль, резистивно-заземлена нейтраль, кратності перенапруг

Citation

Яцейко А. Дослідження перенапруг під час дугових замикань на землю в електромережах 35 кВ / Андрій Яцейко, Олег Горошко // Енергетика та системи керування : матеріали IV Міжнародної конференції молодих вчених EPECS-2013, 21–23 листопада 2013 року, Україна, Львів / Національний університет "Львівська політехніка". – Львів : Видавництво Львівської політехніки, 2013. – С. 12–15. – (4-й Міжнародний молодіжний фестиваль науки "Litteris et Artibus"). – Бібліографія: 6 назв.