Current differential relay with fault location and synchronisation of measurements functions

dc.contributor.authorRosolowski, Eugeniusz
dc.contributor.authorIzykowski, Jan
dc.contributor.authorSaha, Murari Mohan
dc.date.accessioned2013-01-21T08:16:18Z
dc.date.available2013-01-21T08:16:18Z
dc.date.issued2012
dc.description.abstractThis paper considers a fault location and an analytical synchronisation of two-end measurements functions as embedded into a current differential protective relay. As a result of that, incomplete two-end measurements, i.e. a three-phase current measured at both line ends, while a three-phase voltage only from one end are considered as the input signals. The fault location and synchronisation formulae are derived with considering a distributed-parameter model of a transposed overhead line. The performed ATP-EMTP based evaluation has proved the validity of the presented algorithms and their high accuracy. У статті розглядається процедура локалізації несправності та аналітичної синхронізації виміряних на двох кінцях функцій, вбудована у струмове диференційне реле захисту. В результаті цього використовуються неповні вимірювання, проведені на двох кінцях лінії, наприклад, трифазний струм, виміряний на обох кінцях лінії, та трифазна напруга, виміряна лише на одному кінці, подаються як вхідні сигнали. Алгоритм локалізації та формулу синхронізації отримано на підставі моделювання транспонованої повітряної лінії схемою з розподіленими параметрами. Розрахунки, проведені з допомогою ATP-EMTP, підтвердили адекватність запропонованих алгоритмів та їх точність.uk_UA
dc.identifier.citationRosolowski E. Current differential relay with fault location and synchronisation of measurements functions / Eugeniusz Rosolowski, Jan Izykowski, Murari Mohan Saha // Computational Problems of Electrical Engineering. – 2012. – Volume 2, number 1. – P. 111–117. – Bibliography: 7 titles.uk_UA
dc.identifier.urihttps://ena.lpnu.ua/handle/ntb/16437
dc.language.isoenuk_UA
dc.publisherPublishing House of Lviv Polytechnic National Universityuk_UA
dc.subjectoverhead power lineuk_UA
dc.subjectcurrent differential relayuk_UA
dc.subjectfault locationuk_UA
dc.subjecttwo-end measurementuk_UA
dc.subjectanalytic synchronisationuk_UA
dc.subjectATP-EMTP softwareuk_UA
dc.titleCurrent differential relay with fault location and synchronisation of measurements functionsuk_UA
dc.title.alternativeСтрумове диференційне реле із вбудованою процедурою локалізації несправності та синхронізації виміряних функційuk_UA
dc.typeArticleuk_UA

Files

Original bundle

Now showing 1 - 1 of 1
Thumbnail Image
Name:
21-113-119.pdf
Size:
326.8 KB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
2.06 KB
Format:
Item-specific license agreed upon to submission
Description: